Paspatis, A.G., Konstantopoulos, G.C. orcid.org/0000-0003-3339-6921, Mayfield, M. orcid.org/0000-0002-9174-1773 et al. (1 more author) (2018) Current-limiting droop controller with fault-ride-through capability for grid-tied inverters. In: 2017 IEEE PES ISGT Europe Conference Proceedings. 7th IEEE International Conference on Innovative Smart Grid Technologies (IEEE PES ISGT Europe 2017), 26-29 Sep 2017, Torino, Italy. IEEE ISBN 978-1-5386-1954-4
Abstract
In this paper, the recently proposed current-limiting droop (CLD) controller for grid-connected inverters is enhanced in order to comply with the Fault-Ride-Through (FRT) requirements set by the Grid Code under grid voltage sags. The proposed version of the CLD extends the operation of the original CLD by fully utilizing the power capacity of the inverter under grid faults. It is analytically proven that during a grid fault, the inverter current increases but never violates a given maximum value. Based on this property, an FRT algorithm is proposed and embedded into the proposed control design to support the voltage of the grid. In contrast to the existing FRT algorithms that change the desired values of both the real and reactive power, the proposed method maximizes only the reactive power to support the grid voltage and the real power automatically drops due to the inherent current-limiting property. Extensive simulations are presented to compare the proposed control approach with the original CLD under a faulty grid.
Metadata
Item Type: | Proceedings Paper |
---|---|
Authors/Creators: |
|
Copyright, Publisher and Additional Information: | © 2017 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other users, including reprinting/ republishing this material for advertising or promotional purposes, creating new collective works for resale or redistribution to servers or lists, or reuse of any copyrighted components of this work in other works. Reproduced in accordance with the publisher's self-archiving policy. |
Keywords: | Inverter; droop control; current-limiting property; fault-ride-through; voltage sags |
Dates: |
|
Institution: | The University of Sheffield |
Academic Units: | The University of Sheffield > Faculty of Engineering (Sheffield) > Department of Automatic Control and Systems Engineering (Sheffield) The University of Sheffield > Faculty of Engineering (Sheffield) > Department of Civil and Structural Engineering (Sheffield) |
Depositing User: | Symplectic Sheffield |
Date Deposited: | 21 Jul 2017 09:08 |
Last Modified: | 25 Jan 2018 09:21 |
Published Version: | https://doi.org/10.1109/ISGTEurope.2017.8260159 |
Status: | Published |
Publisher: | IEEE |
Refereed: | Yes |
Identification Number: | 10.1109/ISGTEurope.2017.8260159 |
Open Archives Initiative ID (OAI ID): | oai:eprints.whiterose.ac.uk:119299 |