Habibi, M.A., Li, K. and Zhao, Z. (2026) Droop Power Sharing Enhancement of Building Microgrids via Topology Modification. In: 2026 IEEE 9th International Electrical and Energy Conference (CIEEC). 2026 IEEE 9th International Electrical and Energy Conference (CIEEC), 15-17 May 2026, Tianjin, China. Institute of Electrical and Electronics Engineers (IEEE), pp. 3108-3114. ISBN: 979-8-3315-4956-5.
Abstract
This research investigates power sharing enhancement in an islanded microgrid employing two identical Inverter-Based Resources (IBRs) supplying 915 kW total load through droop control. Each IBR is designed with 457.5 kW capacity at 50 Hz, 380 V line-to-line voltage, and 10 kHz switching frequency, featuring LCL filter parameters. The study presents three key components of this study: (1) simulation of the power sharing performance (P/f, Q/V, and delivery efficiency) using real 24-hour load profiles, (2) optimal IBR bus placement strategies, and (3) impact of parallel line additions on microgrid performance. Through comparative analysis of a modified IEEE 5-bus as the benchmark and two proposed topologies, it is shown that the reactive power and voltage stability can be improved notably by slight modifications on the topology. Among the three scenarios, scenario C reduced the reactive power gap by 48% and uplifted voltage level by up to 1.91%. It further boosted the reactive power efficiency by 10.55%, active power efficiency by 1.03% and overall system efficiency by 1.78%, demonstrating that the optimal configuration can enhance the microgrid performance without compromising its stability.
Metadata
| Item Type: | Proceedings Paper |
|---|---|
| Authors/Creators: |
|
| Copyright, Publisher and Additional Information: | This is an author produced version of a conference paper published in 2026 IEEE 9th International Electrical and Energy Conference (CIEEC), made available under the terms of the Creative Commons Attribution License (CC-BY), which permits unrestricted use, distribution and reproduction in any medium, provided the original work is properly cited. |
| Keywords: | power efficiency, distribution network, power sharing, parallel inverter-based resources, load profile |
| Dates: |
|
| Institution: | The University of Leeds |
| Academic Units: | The University of Leeds > Faculty of Engineering & Physical Sciences (Leeds) > School of Electronic & Electrical Engineering (Leeds) |
| Date Deposited: | 03 Nov 2026 16:46 |
| Last Modified: | 04 Nov 2026 11:22 |
| Status: | Published |
| Publisher: | Institute of Electrical and Electronics Engineers (IEEE) |
| Identification Number: | 10.1109/cieec69682.2026.11572169 |
| Sustainable Development Goals: | |
| Open Archives Initiative ID (OAI ID): | oai:eprints.whiterose.ac.uk:247113 |
Download
Filename: 2026073396.pdf
Licence: CC-BY 4.0

CORE (COnnecting REpositories)
CORE (COnnecting REpositories)